Voltage Drop Calculator

Work out how much voltage is lost along a copper or aluminium cable, single-phase, three-phase or DC, and the smallest standard cable size that keeps the drop within your limit.

Rules last checked 25 October 2026Every step shown

Your numbers are saved in this browser.
V

230 V for single-phase in Pakistan, the UK and the Gulf; 400 V between lines for three-phase; 12, 24 or 48 V for most solar batteries.

A
m

From the supply to the load. The return path is counted for you.

%

UK wiring rules allow 3% for lighting and 5% for other circuits; solar installers often aim for 3% or less.

Voltage drop

9.888 V (4.3%)

Drop as a share of supply
4.3%
Voltage at the load
220.112 V
Power lost in the cable
197.76 W
Smallest size within 5%
2.5 mm²

A 30 m run of 2.5 mm² copper at 20 A drops 9.89 V (4.3%), within your 5% limit.

How it's worked out

  1. Voltage drop2 × 30 m × 20 A × 0.0206 Ω·mm²/m ÷ 2.5 mm²9.888 V
  2. Share of supply9.888 ÷ 230 V4.3%
  • Uses conductor resistance at 70 °C and ignores reactance, which is fine for cables up to about 25 mm². The factor 2 counts the cable out and back.
  • Also check the cable's current rating for how it is installed, and follow your local wiring rules. Get a qualified electrician for mains work.

The formula

Single-phase and DC: Vd = 2 × L × I × ρ ÷ A · Three-phase: Vd = √3 × L × I × ρ ÷ A

ρ is the resistivity at a working temperature of 70 °C: 0.0206 Ω·mm²/m for copper and 0.0339 for aluminium. L is the one-way length in metres and A the cable size in mm².

Example

A 30 m run of 2.5 mm² copper carrying 20 A on 230 V drops 9.89 V, which is 4.3%, leaving 220.1 V at the load and wasting about 198 W as heat. That is within 5%; to stay within 3% you would need 4 mm².

Questions people ask

What voltage drop is acceptable?

UK wiring rules allow 3% for lighting and 5% for other circuits from the supply. For solar DC cables, installers often aim for 3% or less to save energy.

How is voltage drop calculated?

For single-phase and DC: 2 × length × current × resistivity ÷ cable area. For three-phase, use √3 instead of 2, which gives the drop between lines.

Why does a long cable need a bigger size?

Resistance grows with length, so a long run loses more voltage and wastes power as heat. A thicker cable has less resistance.

Is this enough to choose a cable?

No. Also check the cable's current rating for the way it is installed and follow your local wiring rules. Mains work should be done by a qualified electrician.